Calculate Lighting Loads
Calculating Lighting Loads
Branch circuits that supply lighting loads are calculated either at
Continuous Duty or
Non-continuous Duty (less than 3 hours of continuous operation).
I (Amperage - also known as Current)
VA (Volt Amp - also known as Watt)
V (Volt)
DF % {Duty Factor for Continuous = 125 %,
for Non-continuous = 100 %}
Formula to Use:
I = (VA * DF %) / V
_________________________________________________________ Branch Circuits that supply
Non-continuous Duty loads (i.e. lamps, etc.) are calculated at 100 % of the total VA of the circuit.
Example:
How many receptacles (outlets) are allowed on a 15 Amp, 120 Volt, 1 Phase circuit; used at Non-continuous duty?
Answer. Use :
I = (VA * 100%) / V
(1st Step)
I = (180 VA * 100 %) / 120 V = 1.5 Amp per outlet.
(2nd Step)
15 Amp (Breaker) / 1.5 Amp = 10 Receptacles
So the total amount of receptacles you can put on a 15 Amp circuit is 10.
Branch Circuits that supply Continuous Duty
loads (i.e. lamps, etc.) are calculated at 100 % of the total VA of the circuit;
In other words, the OCPD (circuit breaker) will be rated at 125 % of the
total load. Example:
How many receptacles (outlets) are allowed on a 15 Amp, 120 Volt, 1 Phase circuit; used at Continuous duty?
Answer. Use :
I = (VA * 125%) / V
(1st Step)
I = (180 VA * 125 %) / 120 V = 1.875 Amp per outlet
(2nd Step)
15 Amp (Breaker) / 1.875 Amp = 8 Receptacles
So the total amount of continuous duty receptacles you can put on a 15 Amp circuit is 8.
Terms of Use - Disclaimer
Return to Electrical Calculations from Calculate Lighting Loads

|